← Tilbage til Dimensionering

Tabel B.52.3

Strømværdier i ampere for installationsmetoder i tabel B.52.1 – XLPE-eller EPR-isolering/to belastede ledere, kobber eller aluminium

Nominelt leder-tværsnit mm² Installationsmetode i tabel B.52.1
A1 A2 B1 B2 C D1 D2
1 2 3 4 5 6 7 8
Kobber
1,51918,52221242727
2,526243028333535
434324038454646
644415148585657
1061577066807577
168074948810797100
2510598124115141126130
35130120153141174151157
50157145185170211180187
70199183236216270222231
95242222287262329265276
120280256333303383303316
150321293382347442343357
185367334438396509387404
240433393518467605449470
300497450596536699510534
Aluminium
2,52018,523222627-
4262531293536-
6343240374544-
10474455516259-
1662577368847677
258176978911098100
3510193120110136118120
50122112146133165141144
70156143187170212174179
95190174228207259209215
120220201265240302239246
150253230305275349271279
185290263350315402307317
240343311416373482359371
300395357480429558403417

NOTE 1: kolonne 3, 5, 6, 7 og 8 er det antaget, at ledere er runde for tværsnit til og med 16 mm. Værdier for større tværsnit gælder for sektorformede ledere og kan med sikkerhed anvendes for runde ledere.